Schwalbacher Straße 49-53

Cologne, Germany

Code: CS40

Project after renovation
© Passive House Institute

© Passive House Institute

Résumé

Renovation of a multi-story residential buildings of the 1950s and 1960s.

Original situation

The building is typical of the multi-story residential buildings of the 1950s and 1960s in Germany. Masonry walls and reinforced concrete floors form the supporting structure. The buildings have flat roofs and basements. Only the roof is insulated with 14 cm of EPS. The original building has balconies that are not insulated.

Heating in the original state is provided by central gas heating. Ventilation is provided by opening windows. There is no active cooling in the building.

Renovation approach

Modernisation proposal

The building will be upgraded with a new wooden façade featuring vertical larch cladding and cellulose fibre insulation. The façade is going to be constructed on-site (no prefabrication). The old masonry wall will stay; the new façade goes on it.

Certain construction work will be carried out on-site by a craftsman’s company, including the integration of new windows with the existing structure. Additional insulation will be applied to the basement walls, especially the ones encompassing the staircase, and the basement ceiling will be insulated from below.

The roof structure will be newly built. The original flat roof structure will stay, and a new pitched roof is going to be constructed on top of it. The new wooden roof structure will be insulated with blow-in straw insulation. A photovoltaic system will be installed on the roof to enhance energy efficiency.

The balconies will be walled up in order to prevent considerable heat loss.

Heating and hot water are supplied by a central heating system that serves the whole building. The heat is generated by an energy-efficient air/water heat pump.

The new mechanical ventilation system with heat recovery will supply fresh air to the building.

Efficiency improvement

The planned renovation works are set at a really high level (by architects). An even lower level (e.g., just to meet EnerPHit standards) would suffice to achieve significant improvement in the building.

Renovation measures will reduce heating demand by more than 90%.

Predicted energy savings:

Savings In space heating demand: 98 [kWh/(m²a)]

Savings Primary Energy Demand: 126 [kWh/(m²a)]

Savings PER Demand: 216 [kWh/(m²a)]

Savings of Final energy demand gas: 139 [kWh/(m²a)]

PHPP verification sheet before retrofit

PHPP verification sheet after retrofit

PHPP verification sheet before retrofit

TFA existing treated floor area (usable floor space)

2500.0 m2

Space heating Heating demand

105.0 kWh/(m2a)

Heating load

51.0  W/m2

Space cooling Cooling & dehum. demand

– kWh/(m2a)

Cooling load

– W/m2

Frequency of overheating (> 25 °C)

1.0 %

Frequency of excessively high humidity (> 12 g/kg)

0.0 %

Airtightness Pressurization test result n50

– /h

Non-renewable Primary Energy (PE) PE demand

187.0 kWh/(m2a)

Primary Energy Renewable (PER) PER demand

257.0 kWh/(m2a)

Generation of renewable energy (in relation to projected building footprint area)

0.0 kWh/(m2a)

EnerPHit classic

no

PHPP verification sheet after retrofit

TFA existing treated floor area (usable floor space)

2500.0 m2

Space heating Heating demand

7.0 kWh/(m2a)

Heating load

6.0  W/m2

Space cooling Cooling & dehum. demand

– kWh/(m2a)

Cooling load

– W/m2

Frequency of overheating (> 25 °C)

12.0 %

Frequency of excessively high humidity (> 12 g/kg)

0.0 %

Airtightness Pressurization test result n50

– /h

Non-renewable Primary Energy (PE) PE demand

61.0 kWh/(m2a)

Primary Energy Renewable (PER) PER demand

41.0 kWh/(m2a)

Generation of renewable energy (in relation to projected building footprint area)

153.0 kWh/(m2a)

EnerPHit classic

no

Key facts

Building typology

Multi family dwelling

Existing treated floor area (usable floor space)

2 500 m2

Consulting outphit partner

Passive House Institute

Project status

Planning phase