Adourable Bagnères, a semi prefabricated EnerPHit

Bagnères de Bigorre, France

Code: CS7

Inside view of the tea room
© F. COLAS, ADOURABLE Bagneres
Outside view before the retrofit
© F. COLAS, ADOURABLE Bagneres
Look into the courtyard
© F. COLAS, ADOURABLE Bagneres
Look inside a hotel room
© F. COLAS, ADOURABLE Bagneres

Original situation

A four storey non-residential building from the 1830s located in the dense city centre of Bagnères de Bigorre in the Pyrenean piedmont (FR-65000).

Renovation approach

Just finished checking structural integrity in preparation for the retrofit; likely finsihed in 2024, started in 2022.

 

Renovation approach document

Modernisation proposal

Semi prefabricated complete retrofit to the EnerPHit Standard. The front side will be a traditional retrofit since the building is listed. The back side will be a prefabricated, compressed straw wall (Ecococon Wall). New triple glazed windows, heat pumps and ventilation with heat recovery will be added.

Efficiency improvement

The planned renovation will bring heating demand down by a factor of more than 20 and also result in an impressive reduction in total primary energy.

PHPP verification sheet before retrofit

TFA existing treated floor area (usable floor space)

250.0 m2

Space heating Heating demand

354.0 kWh/(m2a)

Heating load

114.0  W/m2

Space cooling Cooling & dehum. demand

0.0 kWh/(m2a)

Cooling load

0.0 W/m2

Frequency of overheating (> 25 °C)

0.0 %

Frequency of excessively high humidity (> 12 g/kg)

1.0 %

Airtightness Pressurization test result n50

1.0 /h

Non-renewable Primary Energy (PE) PE demand

455.0 kWh/(m2a)

Generation of renewable energy (in relation to projected building footprint area)

881.0 kWh/(m2a)

PHPP verification sheet after retrofit

TFA existing treated floor area (usable floor space)

250.0 m2

Space heating Heating demand

15.0 kWh/(m2a)

Heating load

8.0  W/m2

Space cooling Cooling & dehum. demand

0.0 kWh/(m2a)

Cooling load

0.0 W/m2

Frequency of overheating (> 25 °C)

10.0 %

Frequency of excessively high humidity (> 12 g/kg)

5.0 %

Airtightness Pressurization test result n50

1.0 /h

Non-renewable Primary Energy (PE) PE demand

26.0 kWh/(m2a)

Generation of renewable energy (in relation to projected building footprint area)

12.0 kWh/(m2a)

Key facts

Building typology

Multi family dwelling

Existing treated floor area (usable floor space)

250 m2

Building owner

Adourable Bagnères SARL

Consulting outphit partner

PROPASSIF

Project status

Construction phase

Overall budget

400 000 €